Reparatur der Absperrklappe

Reparatur der Absperrklappe

Reparatur der Absperrklappe

Butterfly valves are simple and reliable, they do not require technical maintenance during operation, and they usually fail due to improper installation. Below is a list of possible malfunctions and the procedure for repairing disc valves.

Possible malfunctions and their remedies

Malfunction Cause Remedy
Non-hermetic valve closure Polymer insert damaged Damage can occur if welding work was carried out near the butterfly valve, or if it was installed in the closed position, requiring excessive force to open. Another cause of damage may be carbonate deposits on the disk surface, typical for hot water supply systems.
Remove the valve and replace the insert.
- // - Deformed polymer insert Deformation of the polymer insert may occur during improper installation, for example, if the valve had to be inserted between the flanges with tension, or if it was in the closed position during installation.
Drain the pipeline, remove the valve, straighten the polymer insert, and reinstall it.
Unable to open (jammed) Disk clamped by polymer insert Drain the pipeline, loosen the flange nuts, open the butterfly valve by one quarter, and tighten the bolts.
Unable to close completely Flow part is contaminated. Typical for butterfly valves with a vertical stem position Drain the pipeline, remove the valve and clean the flow part.
- // - Polymer insert (gasket) damaged See above.
Leakage between flanges and housing The planes of the corresponding flanges are not parallel They should be parallel.
- // - Additional gasket inserted Gaskets between the valve flange and housing are not necessary. The polymer insert of the valve serves as a gasket.
- // - Polymer insert (gasket) damaged See above.
- // - Bolts not tightened No comments
Leakage from the shock absorber Damaged or missing shock absorber seal Drain the pipeline, remove the retaining ring that holds the shock absorber seal and replace the seal

Frage : Kommentar : Rückmeldung

wo über die Antwort benachrichtigen. wird nirgendwo veröffentlicht

65

DN
Nennweite DN
mm
PN
Nennbetriebsdruck PN
bar
Ihr Produkt dem Katalog hinzufügen

Gemeinschaft von Experten

Wir sammeln eine Gemeinschaft von Experten für die Planung, Installation und Wartung von Heizungs-, Warmwasser- und Wasserversorgungssystemen in Land of dreams. Treten Sie der Gemeinschaft bei und Sie erhalten E-Mails mit Arbeitsanfragen in Land of dreams von unseren Besuchern.

Planung
Installation
Wartung
Heizung
Wasserversorgung
Klimaanlage
Werbung auf der Website
3 190 visitors yesterday
visitors per month
6 from Land of dreams
49 243 from all countries