Maintenance of the check valve

Maintenance of the check valve

The frequency and scope of maintenance are determined by technical personnel depending on the operating conditions of the check valve. It is recommended to check the valve's performance at least once a month.

Possible malfunctions and troubleshooting methods

Malfunction Cause

Solution
No flow The pressure difference across the valve disc is less than the opening pressure Increase the pressure before the check valve or decrease the pressure after it
-//- The plug or stopper of the passage was not removed during installation Disassemble the check valve and remove the plug/stopper
The valve is not sealing properly The seat or disc is damaged Replace the check valve
-//- A solid particle is stuck under the disc 1. Try to flush out the particle by repeatedly opening/closing the shut-off valve near the check valve.
2. Drain the pipeline, disassemble the valve, and remove the particle.
The check valve is knocking The valve diameter is too large 1. Install a smaller diameter valve
2. Install a disc damper (this option is available only for some types of check valves)
-//- - high flow turbulence
- the check valve is installed too close to the pump
- pipeline vibration
Change the installation location of the check valve
Check valve flange failure The valve is subjected to stresses from the connected pipelines Relieve the valve body by installing additional supports or thermal expansion compensators
-//- Bolts are unevenly tightened or flanges are misaligned Perform even bolt tightening, correct flange misalignment

question : comment : feedback

where to notify about the reply. not published anywhere

136

DN
Nominal diameter DN
mm
PN
Nominal pressure PN
bar
add your product to the catalog

community of experts

We are gathering a community of experts in the design, installation, and service of heating, hot water, and water supply systems in United States. Join the community and you will receive emails with requests for work in United States from our visitors.

design
installation
service
heating
water supply
conditioning
dealers
advertising on the website
3 623 visitors yesterday
visitors per month
23 501 from United States
73 417 from all countries