Malfunction | Cause | Correction |
---|---|---|
Low power | 1. Low fuel combustion heat or high fuel moisture. | Use recommended fuel with defined moisture content. |
-//- | 2. Low draft. | Check the draft in the flue and the compliance of the pipe with the manufacturer's recommendations. |
-//- | 3. Soot deposits in the gas passages and/or flue gas collector. | Clean the surface of the furnace and flue passages from accumulated soot. |
-//- | 4. Scale deposits on the internal surface of the boiler. | Scale appears if the boiler was fed with unprepared water. Clean the boiler from scale. The most effective method of cleaning from scale is chemical cleaning. |
A large amount of condensate forms on the walls of the boiler furnace, and black liquid flows out through the loading or ash door. | Low water temperature at the inlet of the boiler. | The water temperature at the inlet of the boiler should exceed 65°C. Check the operation of the mixing valve on the bypass bridge. |
It is impossible to regulate the operation of the boiler. | 1. The ash door does not close tightly. | Check the sealing cord and the door fastener. |
-//- | 2. Strong draft in the chimney and/or high heat output of the fuel. | Adjust the chimney damper. Install a draft limiter. |
The temperature of the flue gases exceeds the passport values. | Strong draft in the chimney and/or clogged heat transfer surfaces. | Adjust the chimney damper. Clean the surfaces of the furnace and flue passages from soot and resin. |
question : comment : feedback
answer
145
2 659 | visitors yesterday |
visitors per month | |
46 | from Land of dreams |
74 238 | from all countries |