Sonometer 2000 Infocal 5 Danfoss
Heat meter

production of discontinued

calculation and selection
100 % - model rating
Drawing Sonometer 2000 Infocal 5 Danfoss Heat meter Design Sonometer 2000 Infocal 5 Danfoss Heat meter Scheme Sonometer 2000 Infocal 5 Danfoss Heat meter
Model
Sonometer 2000 Infocal 5
Manufacturer
Country
Denmark
Сalculator
INFOCAL 5 OS
Accuracy class according to EN 1434-1
2
Construction
modular construction
Power supply
from power element (battery)
Yearly archive
15 years
Monthly archive
36 months
Daily archive
360 days
Archive by hours
4320 hours
Downtime
registers
Error registration
registers
Data retrieval
optical interface
Temperature difference Max
150 °C
Temperature difference Min
2 °C
Temperature sensor
Pt500
Length of the sensor
27,5 / 50 mm
Tmax
180 °C
Tmin
0 °C
Standard cable length
- m
Maximum cable length
10 m
Flow sensor
Sono 1500 CT DN15-32 | Sono 2500 CT DN40-80
Type
ultrasonic
Dynamic range
1:250 DN15-32 | 1:100 DN40-80
Standard cable length
2,5 m
Maximum cable length
10 m
PN
25 / 16
Tmax
90/130/150 DN15-32 | 120/150 DN40-80
Tmin
5 DN15-32 | 20 DN40-80

technical
specifications
price

DN
mm
Qn
m³/h
Qt
m³/h
Qmin
m³/h
Qmax
m³/h
dP
kPa
L
mm
DN 'Up'
DN 'Down'
price
15 G 0.6
1.0
1.5
-

-

-

0.006

0.01

0.006

1.2

2.0

3.0

9.5

4.2

9.5

110

110

110

not required
not required
production of discontinued


20 G 0.6
1.0
1.5
2.5
-

-

-

-

0.006

0.01

0.006

0.01

1.2

2.0

3.0

5.0

8.5

3.6

7.5

10.0

130/190

130/190

130/190

130/190

not required
not required
production of discontinued



20 FL 0.6
1.0
1.5
2.5
-

-

-

-

0.006

0.01

0.006

0.01

1.2

2.0

3.0

5.0

8.5

3.6

7.5

10.0

190

190

190

190

not required
not required
production of discontinued



25 G 3.5
6.0
-

-

0.35

0.024

7.0

12.0

4.4

12.8

260

260

not required
not required
production of discontinued

25 FL 3.5
6.0
-

-

0.035

0.024

7.0

12.0

4.4

12.8

260

260

not required
not required
production of discontinued

32 FL 3.5
6.0
-

-

0.035

0.024

7.0

12.0

4.4

12.8

260

260

not required
not required
production of discontinued

40 FL 10.0
-

0.100

20.0

5.0

300

5DN
not required
production of discontinued
50 FL 15.0
-

0.150

30.0

6.0

270

5DN
not required
production of discontinued
65 FL 25.0
-

0.250

50.0

7.0

300

5DN
not required
production of discontinued
80 FL 40.0
-

0.400

80.0

10.0

300

5DN
not required
production of discontinued

DN - nominal diameter (FL, G - flanged and threaded execution), mm.

Qn - nominal flow rate, m³/h.

Qt - transitional flow rate, m³/h.

Qmin - minimum flow rate, m³/h.

Qmax - maximum flow rate, m³/h.

dP - pressure loss across the flow meter at nominal flow rate, kPa.

L - length along the pipeline axis, mm.

DN 'Up' - the minimum required length of straight pipe upstream of the flowmeter necessary to ensure measurement accuracy, in nominal diameters, mm.

DN 'Down' - also downstream of the flow meter, mm.

question : comment : feedback

where to notify about the reply. not published anywhere
Water flow rate
m³/h
add your product to the catalog

community of experts

We are gathering a community of experts in the design, installation, and service of heating, hot water, and water supply systems in United States. Join the community and you will receive emails with requests for work in United States from our visitors.

design
installation
service
heating
water supply
conditioning
dealers
advertising on the website
4 090 visitors yesterday
visitors per month
28 256 from United States
74 238 from all countries
add your company to the catalog