Installation of auto bypass valves

Installation of auto bypass valves

Installation of bypass valve should be performed in accordance with the installation instructions and taking into account the recommendations below.

  • A strainer filter is recommended to be installed before the bypass valve.
  • Pressure gauges should be installed before and after the valve to monitor the activation pressure.
  • The bypass valve body should not be subjected to tension, torsion, bending, or compression loads from connected pipelines.
  • Different manufacturers provide different data, but on average, it is recommended to maintain straight sections of 5DN before and 10DN after the valve.
  • The bypass valve can be installed on a horizontal, vertical, or inclined pipeline, unless otherwise specified in the installation instructions.

question : comment : feedback

where to notify about the reply. not published anywhere

143

Kvs
Flow coefficient
m³/h
Setting pressure
bar
add your product to the catalog

community of experts

We are gathering a community of experts in the design, installation, and service of heating, hot water, and water supply systems in United States. Join the community and you will receive emails with requests for work in United States from our visitors.

design
installation
service
heating
water supply
conditioning
dealers
advertising on the website
4 090 visitors yesterday
visitors per month
28 256 from United States
74 238 from all countries