Panel de control para bombas

Panel de control para bombas

The connection of the pumping unit to the electrical network should be carried out through a panel that performs the functions of protection and control of pumps.

The illustration shows a basic diagram of a control panel for two pumps installed in the circulation loop of the heating system, with a minimum set of functions for protection and automation of the pumping unit.

Protection

The pump control panel should provide the following basic protection:

  • Dry run protection - the pump is switched off when the pressure in the suction pipe falls below the set value.
  • Phase voltage unbalance protection - power supply to the pump is switched off in case of unacceptable phase voltage unbalance.
  • Motor overload protection (thermal protection) - activated in case of shaft blockage and overload.

Control

Depending on the technological process conditions, the control panel may implement the following automation functions:

  • Manual and automatic control depending on various conditions.
  • Activation of a backup pump in case of failure of the working one.
  • Automatic switching of operation from a backup to a working pump, thus ensuring even load and wear.
  • Cascade pump activation based on a time schedule or deviation of a controlled parameter (such as flow rate or pressure) from a set value.
  • Maintaining a constant flow rate, pressure or head behind the pump is achieved by installing a frequency controller.
  • Blocking the pump start-up when the set frequency of activation is exceeded or depending on other conditions.

pregunta : comentario : opinión

dónde notificar sobre la respuesta. no se publica en ningún lugar

41

Caudal de agua
m³/h
Presión
m
añadir su equipo al catálogo
descatalogado
GD
Speroni

comunidad de expertos

Estamos formando una comunidad de expertos en diseño, instalación y servicio de sistemas de calefacción, agua caliente y suministro de agua en United States. Únete a la comunidad y recibirás emails con solicitudes de trabajo en United States de nuestros visitantes.

diseño
instalación
servicio
calefacción
suministro de agua
acondicionamiento
publicidad en el sitio web
3 190 visitors yesterday
visitors per month
17 891 from United States
49 243 from all countries