Esquemas de instalación de los reguladores de presión diferencial

Pressure regulators closing on pressure increase

Esquemas de instalación de los reguladores de presión diferencial

In heating and cooling systems with varying flow rates, pressure differential regulators on branches (risers, horizontal branches) allow to eliminate the influence of hydraulic regime fluctuations on the branch. They prevent noise generation on regulating valves at high throttling head. They allow to optimize regulation by increasing the 'authority' of regulating valves.

Diagram of installation of a differential pressure regulator in a thermal point

Pressure differential regulators installed in front of regulating valves allow to eliminate noise generation caused by high throttling head and optimize regulation by increasing the 'authority' of the regulating valve. When impulse tubes are connected before and after the regulating valve, the pressure differential regulator allows to set the calculated flow rate and does not allow its excess.

Pressure regulators opening on pressure increase

Diagram of installation of a differential pressure regulator in a pump system

On the bypass line of the circulation pump in systems with highly variable flow rates. When the flow rate decreases in the system, and consequently through the pump, the head created by the pump increases, and therefore the pressure differential between the suction and discharge nozzles increases. The regulator reacts to the increase in pressure differential and opens, allowing the heat transfer agent to flow from the discharge nozzle to the suction nozzle, thereby maintaining a constant flow rate through the pump.

Diagram of installation of a differential pressure regulator in a boiler room

In the jumper between the supply and return pipelines in the non-condensing boiler system connected to a system with a dynamic hydraulic regime, a pressure differential regulator is necessary to create an optimal boiler operating mode. As the flow rate decreases, the head created by the pump in the system increases, and consequently, the pressure differential between the supply and return pipelines of the boiler room increases. The regulator reacts to the increase in pressure differential and opens, allowing the hot heat transfer agent from the supply pipeline to flow to the return pipeline, providing a stable flow rate through the boiler regardless of fluctuations in the system. This scheme of using a pressure differential regulator increases the water temperature at the inlet to the boiler, reducing the likelihood of condensation of exhaust gases on the heat exchange surface.

* Explicación de los símbolos gráficos condicionales en los diagramas

pregunta : comentario : opinión

dónde notificar sobre la respuesta. no se publica en ningún lugar

79

Kvs
Coeficiente de flujo
m³/h
Presión de ajuste
bar
añadir su equipo al catálogo

comunidad de expertos

Estamos formando una comunidad de expertos en diseño, instalación y servicio de sistemas de calefacción, agua caliente y suministro de agua en United States. Únete a la comunidad y recibirás emails con solicitudes de trabajo en United States de nuestros visitantes.

diseño
instalación
servicio
calefacción
suministro de agua
acondicionamiento
publicidad en el sitio web
3 190 visitors yesterday
visitors per month
17 891 from United States
49 243 from all countries