Réglage du régulateur de débit d'eau

Setting up a water flow regulator of direct action is carried out after filling the pipeline with water during the commissioning of the entire system. If the required flow is known precisely, and the position on the adjustment scale is clearly defined, it is permissible to adjust the flow regulator before filling the pipeline with water.

The flow regulator is adjusted by rotating the handle that changes the hydraulic resistance of the throttle until the flow is aligned with the desired value. To facilitate the flow adjustment and monitor the regulator's operation, it is necessary to install a pressure gauge at the impulse intake point.

The accuracy of maintaining the water flow is checked by a direct method using a flow meter installed on the same pipeline, or indirectly, for example, in the case of a heating system, with the known thermal power, the flow can be determined by the temperature difference between the inlet and outlet of the system.

The flow regulator is tested by changing the water pressure before or after it. The water pressure is changed by any regulating or shutoff valve installed on the same pipeline, while paying attention to the speed of the regulator's response and the accuracy of flow maintenance.

question : commentaire : retour

où notifier de la réponse. n'est publié nulle part

47

Débit d'eau
m³/h
ajoutez votre équipement au catalogue

communauté d'experts

Nous réunissons une communauté d'experts dans la conception, l'installation et l'entretien des systèmes de chauffage, d'eau chaude et d'approvisionnement en eau en United States. Rejoignez la communauté et vous recevrez des emails avec des demandes de travail en United States de la part de nos visiteurs.

conception
installation
entretien
chauffage
approvisionnement en eau
climatisation
publicité sur le site web
3 190 visitors yesterday
visitors per month
17 891 from United States
49 243 from all countries