Installation du régulateur de débit d'eau

Automatic direct-acting flow regulators are technically complex pipeline equipment, so before installation, be sure to study the installation instructions and pay attention to the following recommendations:

  • Manometers should be installed before and after the regulator to monitor its performance.
  • It is recommended to install a flow meter on critical sections to monitor the regulator's performance.
  • The regulator housing should not be subject to torsion, stretching, bending or compression from connected pipelines.
  • Flow regulators are unidirectional, so the direction of water flow at the installation site should correspond to the arrow on the housing.
  • Flow regulators should be installed on a horizontal or vertical pipeline, unless prohibited by the installation instructions.
  • Direct-acting flow regulators are very sensitive to the presence of mechanical inclusions in the flowing water, so it is mandatory to install mesh filters in front of them.

Sequence for packing a threaded connection

1. Take a flax fiber string with enough threads so that its twisted diameter is approximately equal to the depth of the thread. The length of the string should provide for 1.5-2 times more windings than the number of thread turns.

2. Starting approximately 50-70 mm from the beginning of the string, slightly twist it, place it in the first thread turn, and, holding it with your hand, tightly wind a long branch of the string clockwise, placing it in each thread turn.

3. When reaching the end of the thread, continue winding with a second layer, shifting the turns to the beginning of the thread. The length of the second layer winding should be approximately equal to 2/3 of the thread length.

4. Wind the remaining end of the string (50-70 mm) similarly clockwise, from the end of the thread to its beginning.

5. Apply a layer of sealant to the winding surface.

6. Tighten the connecting elements by hand. With correct packing, the assembled element should turn 1.5-2 full rotations.

7. Continue tightening the element with a wrench or a torque wrench. In case the assembled element needs to be in a specific position, complete tightening it in the necessary position of the element.

With proper packing, during tightening, the force should not exceed the tightening torque listed below:

DN15 DN20 DN25 DN32 DN40 DN50 DN65 DN80 DN100
70 Nm 95 Nm 120 Nm 150 Nm 190 Nm 230 Nm 280 Nm 350 Nm 400 Nm

Tightening torques for flange connections

DN Nut/Bolt Torque, Nm
15 - 32 М 10 15 - 30
40 - 65 М 12 35 - 50
80 - 100 М 16 75 - 100
125 - 150 М 16 80 - 120
200 М 20 150 - 200
250 - 400 М 24 340 - 410
500 М 27 340 - 410

question : commentaire : retour

où notifier de la réponse. n'est publié nulle part

48

Débit d'eau
m³/h
ajoutez votre équipement au catalogue

communauté d'experts

Nous réunissons une communauté d'experts dans la conception, l'installation et l'entretien des systèmes de chauffage, d'eau chaude et d'approvisionnement en eau en United States. Rejoignez la communauté et vous recevrez des emails avec des demandes de travail en United States de la part de nos visiteurs.

conception
installation
entretien
chauffage
approvisionnement en eau
climatisation
publicité sur le site web
3 190 visitors yesterday
visitors per month
17 891 from United States
49 243 from all countries